Delta Hmi Dop B Usb Driver

DELTA ELECTRONICS. DOP HMI USB Driver (usbser) Ports 15. 5) In this driver, PLC station number represents PLC slot number. Controller Station Number: 1. Control Area / Status Area: B3:0/B3:10. RS-232 (DOP-A/AE/AS, DOP-B Series). Delta HMI can be connected to VLT-2800, 5000, 6000, 7000 controller. Delta HMI DOP-B series - Duration. Delta HMI DOP-B Series Screen. DOP series HMIs support more than twenty brands of external controllers, including Delta, Omron, Siemens, Mitsubishi, etc. More detail you can see on DOPSoft V2. Rapid USB Upload/Download: Not only RS-232, the users also can use DOPSoft V2 to upload and download screen data and programs via USB interface. May 10, 2011 Delta HMI – USB Updating firmware. A few month ago our R&D people develop a new useful feature for DOP-B HMI. Is the possibility to update the firmware of the HMI without any PC (only USB disk!). The procedure is quite simple, take a look to the next video. If playback doesn't begin shortly, try restarting your device. IN THIS VIDEO EXPLAIN HOW TO delta dop hmi program download using usb cablePlaylists: schneider altivar vfd programming VF.

  1. Delta Hmi Dop B Usb Driver Windows 7
  2. Delta Hmi Dop B Usb Driver Download

Only HMISoft V1.18 or later supports Windows 7.

Download the HMISoft version 2.11 from the Eaton website using the link below:

Delta Hmi Dop B Usb Driver Windows 7

To set up Windows 7 Upload/ Download compatibility on an HMI and HMISoft V1.18 or later there are two steps

Step 1- Update the firmware in the HMi. There are possible 4 methods- USB transfer from a Win XP machine, Serial Transfer, Ethernet transfer, and USB memory disk:

USB from a Win XP machine

-Connect USB cable to HMi

Delta Hmi Dop B Usb Driver Download

-In HMISoft select FILE > UPDATE FIRMWARE

Serial Transfer

- In HMISoft, go to OPTIONS > CONFIGURATION Standard tab and set Upload/ Download to PC COM PORT and select the com port number of your RS232 port or converter

Driver

- On your HMI, press and hold the SYS button to get to the system screen, then select DOWNLOAD PORT, then select the com port number on the HMi you're connect to, when asked BYPASS MODE? choose NO

- In HMISoft select FILE > UPDATE FIRMWARE

- Cable Pin Out 2 – 3

3 – 2

5 – 5

7 – 8

HmiDelta Hmi Dop B Usb Driver

8 – 7

Ethernet Transfer (6, 8, 10 inch with HMIECENT ethernet expansion module)

- On the HMi, press and hold the SYS key to get to the system screen, select NETWORK and note the IP address of the HMi

- In HMISoft, go to OPTIONS > CONFIGURATION Standard tab and set Upload/ Download to ETHERNET

- In HMISoft select FILE > UPDATE FIRMWARE, in the dialog box uncheck AUTO SEARCH and enter IP address then click START

USB Disk (4, 8, 10 inch units only)

- Insert a USB Disk formatted FAT32 into your PC

- Open and compile a configuration in HMISoft

- Select FILE > MAKE EXT MEMORY DATA and select the drive letter of your USB Disk

- Insert the USB disk into an HMI and press and hold SYS to get to the system screen

- Select FILE MANAGER and select the icon that looks like an arrow pointing up from an IC chip

Step 2- Set the USBCommMode

- Press and hold the SYS button to get to the system screen.

- Press SETTINGS and scroll down to USBCommMode and use the + key to set the value to 1 for Win 7 compatibility, you must change to 0 for Win XP compatibility. Press the SAVE button then close and enter RUN mode.

You should now be able to perform downloads from your Win 7 PC to HMI via USB.